Sungrow IDC180E
the sungrow charger configuration process is primarily managed remotely by sungrow configuration tip for sungrow dc chargers please note that clemap regulates power based on ac measurement and does not factor in internal ac/dc conversion losses of the chargers in dynamic circuits , this is not an issue the system reacts in real time to total load and automatically adjusts the charging power if limits are approached in static circuits , however, the system cannot detect internal conversion losses in the worst case scenario , sungrow chargers can have a conversion efficiency of 92% to maintain full compliance, we recommend applying a simple safety margin in the configuration example for a 200 a breaker, account for the 8% efficiency loss 200 a (1 0 92) = 16 a set the security margin to 16a this small adjustment ensures the system runs safely and efficiently even under high load conditions since the configuration is performed remotely by sungrow, you’ll need to contact their support team here’s what you should do send an email or raise a support ticket with sungrow support provide them with the necessary details about your charger, such as charger model and serial number confirmation of your setup with clemap load management request modbus activation on the charger to enable communication with the clemap system the gateway address 192 168 1 1 should preferably not be used in the router, as it is internally reserved by the charger instead, choose a different gateway, such as 192 168 2 1 , to prevent conflicts configure the idc 180e in the clemap load management happy charging!