Charging Station Configuration...

Alpitronic Hypercharger

Typical Hypercharge configuration on local Hypercharge webinterface. MobBus Enabled shall be set to True. Grid Fallback Timeout shall be set to 5 seconds.

Hypercharge configuration
Hypercharge configuration


Eventually call the alpitronic service desk so that they activate modbus on your charger from their backend: +3904711961333

Enter the Hypercharge IP Address and Port 502 on the CLEMAP Load Management configuration page.

Example of Hypercharge configuration
Example of Hypercharge configuration