Mennekes AMTRON Professional
1) Enter webUI using the charging station’s IP Address or IP_ADDR:25000.
2) You can change language clicking the flag in the top right corner.
3) At the LAN tab you can set a fixed IP Address for the station.
4) Leave DHCP switched on at the charging station and save a fixed IP address in the router. You can also choose a static one to make sure it does not change in the future.
5) For certain versions you will have to activate the Modbus TCP Server and set the Register Address Set on MENNEKES.
6) The setting "Dynamic Load Management - DLM Master/Slave" must be set to "DLM Master (With internal DLM Slave)".
7) Please check that in the installation tab, that the Installation Current Limit is set to your needs.
8) Also please check that in the load management tab, the Operator Current Limit is set to your needs.
Happy charging!